Tuesday, 17 October 2017

Arc current at 5.5 m/s


Arc current at 5.5 m/s


The total period of the arc for the contact
opening velocity at 5.5 m/s is about 6000 μs.
The peak of arc current is about 2400 A. This
is higher than the arc current at contact
opening velocity of 10 m/s.


Ref: Piezoelectrics in Circuit Breakers: Design & Test

Wednesday, 20 September 2017

Dr Kesorn Pechrach Weaver: Piezoelectrics in Circuit Breakers: Opportunity: direct electromechanical coupling of ...

Dr Kesorn Pechrach Weaver: Piezoelectrics in Circuit Breakers: Opportunity: direct electromechanical coupling of ...: Opportunity The direct electromechanical coupling of a piezoelectric actuator means that it would be possible to tailor the contact ope...

Opportunity: direct electromechanical coupling of a piezoelectric


Opportunity

The direct electromechanical coupling of a
piezoelectric actuator means that it would be
possible to tailor the contact opening
trajectory simply by controlling the charge
on the actuator. It is known that the opening
velocity profile can have a significant effect
on the contact erosion [36, 37], and it may
therefore be possible to optimize the contact
opening trajectory for minimum contact
erosion. This is an important area for further
study.
These initial results show that despite a low
contact opening velocity on the
piezoelectrically operated contacts (due to
the large mass of the moving contact) the
transition to rapid arc motion away from the
contact region occurs only slightly later than
the constant velocity system. Clearly the
contact mass is a significant factor in the
speed of operation of the contact system.

Ref: Piezoelectrics in Circuit Breakers: Design & Test

Thursday, 20 July 2017

Dr Kesorn Pechrach Weaver: Piezoelectrics in Circuit Breakers: How to Measure the Arc Pressure

Dr Kesorn Pechrach Weaver: Piezoelectrics in Circuit Breakers: How to Measure the Arc Pressure: How to Measure the Arc Pressure Two pressure transducers are used to monitor the gas pressure in the arc chamber. The SX series of pie...

How to Measure the Arc Pressure


How to Measure the Arc Pressure


Two pressure transducers are used to
monitor the gas pressure in the arc chamber.
The SX series of piezo resistive pressure
sensor functions as a wheatstone bridge on a
silicon chip with a response times of 0.1 ms.
The pressure transducer gives a voltage output directly proportional to the applied
pressure with sensitivity 0.75 mV/Psi. Long
term stability is 0.1% and repeatability is
0.5% (Maximum difference in output at any
pressure with the operating pressure range
and temperature within O °C to +70 °C).
Resistors are ion implanted into the silicon.
The cavity etched on the reverse to create a
thin silicon diaphragm.

Reference: Piezoelectrics in Circuit Breakers: Design & Test 



Friday, 16 June 2017

Dr Kesorn Pechrach Weaver: Piezoelectrics in Circuit Breakers: How to use Solenoid and Piezoelectric in Circuit B...

Dr Kesorn Pechrach Weaver: Piezoelectrics in Circuit Breakers: How to use Solenoid and Piezoelectric in Circuit B...: Solenoid and Piezoelectric in Circuit Breakers The waveform of arc voltage and contact position when the contact opening velocity of 1 ...

How to use Solenoid and Piezoelectric in Circuit Breakers

Solenoid and Piezoelectric in Circuit Breakers


The waveform of arc voltage and contact
position when the contact opening velocity
of 1 m/s, using solenoid and piezoelectric as
mechanism to open the contacts, as shown in
Figure 8.4.

From figure 8.5, on the 1 m/s moving
contact, the anode moves rapidly 2.5 mm
after 1 m/s at a contact gap of 0.6 mm, after
this movement the anode root remains static
for 2ms until the arc transfers rapidly away
from the contact region, at a contact gap of
2.5 mm.

Reference: Piezoelectrics in Circuit Breakers: Design & Test by Dr Kesorn Pechrach Weaver PhD